Compression repair sleeves

Type Conductor diameter [mm] Identity number a [mm] D [mm] Weight [kg]
163407.1 15.6 - 17.0 36 AlFe 192 36 0.36
163409.1 18.7 - 20.4 36 AlFe 192 36 0.31
163401 20.5 - 21.8 36 AlFe 192 36 0.30
163403.2 24.0 - 25.4 45 AlFe 236 45 0.60
163403 25.4 - 27.2 45 AlFe 236 45 0.60
163403.4 27.21 - 28.19 45 AlFe 236 45 0.57
163404.1 27.3 - 28.1 52 AlFe 219 52 0.78
163404 28.2 - 29.3 52 AlFe 219 52 0.78
163405 29.6 - 30.8 56 AlFe 219 56 0.95
163406 35.5 - 36.7 60 AlFe 244 60 1.08
163436 Gannet 25.76 45 AlFe 236 45 0.60
163403.1 28.1 45 AlFe 236 45 0.57
163440 Pastel 412 26.4 52 AAAC 340 52 1.26
163750 AlFe 400/52 27.6 52 AlFe 190 52 0.68
163417 Drake 28.11 52 AlFe 190 52 0.68

 

Material
Aluminium
Surface protection
Chemically burnt
Use
Repairing of ACSR and Al conductors if number of damaged wires does not exceed 1/3 of the outer layer and damage is to be found in the lenght of triple diameter of conductor in maximum. It keeps 85% of nominal Breaking load of the conductor at the place of repair