Compression strain clamps
Type | Conductor cross section [mm^2] | Conductor diameter [mm] | Identity number Fe joint | Identity number Al joint | a [mm] | D1 [mm] | D2 [mm] | IthN [kA] | Strenght of attachment [kN] | Weight [kg] |
---|---|---|---|---|---|---|---|---|---|---|
176609.1 | 95/15 | 13.6 | 10 Fe | 25 AlFe | 265 | 10 | 25 | 25 | 28.2 | 0.62 |
176617.1 | 150/25 | 17.1 | 14 Fe | 32 AlFe | 375 | 14 | 32 | 25 | 43.3 | 1.02 |
176619.2 | 185/31 | 19.08 | 16 Fe | 36 AlFe | 375 | 16 | 36 | 40 | 55.2 | 1.25 |
176622.1 | 240/40 | 21.9 | 16 Fe | 36 AlFe | 394 | 16 | 36 | 40 | 68.7 | 1.15 |
176635.2 | 350/6 | 26.5 | 24 Fe | 45 AlFe | 487 | 24 | 45 | 40 | 103.0 | 2.11 |
Material
Aluminium, aluminium alloy, steel
Surface protection
Aluminium chemically burnt, steel and jointing material hot dip galvanized
Use
Anchoring of ACSR conductors with greased as well as non-greased core, applied on overgead lines and substations
Note
* Conductor with greased both Fe core as well as Al layer