Compression strain clamps
Type | Conductor cross section [mm^2] | Conductor diameter [mm] | Identity number Fe joint | Identity number Al joint | d [mm] | a [mm] | c [mm] | D1 [mm] | D2 [mm] | IthN [kA] | Strenght of attachment [kN] | Al tube connector Type | Weight [kg] |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
175075.1 | 750/43 | 36.5 | 20 Fe | 60 AlFe | 19 | 673 | 40 | 20 | 60 | 40 | 131.5 | 616075 | 5.20 |
175075.5 | 750/43 | 36.5 | 20 Fe | 60 AlFe | 22 | 673 | 40 | 20 | 60 | 50 | 131.5 | 616075 | 5.27 |
175081.1 | 758/43 | 36.5 | 20 Fe | 60 AlFe | 19 | 724 | 40 | 20 | 60 | 40 | 139.2 | 616081.2 | 5.39 |
175876.1 | AlFe 679-AL1/86-ST1A | 36.2 | 26 Fe | 60 AlFe | 19 | 693 | 40 | 26 | 60 | 40 | 166.8 | 616876.2 | 5.64 |
Material
Aluminium, aluminium alloy, steel
Surface protection
Aluminium chemically burnt, steel and jointing material hot dip galvanized
Use
Anchoring of ACSR conductors with greased as well as non-greased core, applied on overgead lines and substations
Note
*Conductor with greased both Fe core as well as Al layer Conductor with greased both Fe core as well as Al layer